Sensible Thermal Power Calculator

Calculate sensible heating/cooling power: Q = ṁ × c_p × ΔT. For HVAC air handling unit sizing and heat exchanger preliminary design. Referenced standards: UNI EN ISO 13790, UNI 10339 Impianti aeraulici. Technical support tool. Results do not replace design verification by a licensed professional engineer.

Notice: Technical support tool. Results do not replace design verification by a licensed professional engineer.

Calculator

Input parameters

Portata massica del fluido in kg/s (acqua: 1 l/s = 1 kg/s)

Calore specifico del fluido: acqua ≈ 4186, aria ≈ 1005, glicole etilenico 50% ≈ 3600 J/(kg·K)

Variazione di temperatura del fluido (ingresso-uscita) in Kelvin o gradi Celsius

Results
Potenza termica (W) W

Potenza termica scambiata in Watt

Potenza termica (kW) kW

Potenza termica scambiata in Kilowatt

How it works

Formula
Q [W] = ṁ [kg/s] × cp [J/(kg·K)] × ΔT [K]

La potenza termica scambiata per calore sensibile è Q = ṁ × cp × ΔT, dove ṁ è la portata massica, cp il calore specifico del fluido e ΔT la variazione di temperatura. Questa formula è alla base del dimensionamento di scambiatori di calore, caldaie, pompe di calore e impianti idronici.

Assumptions and conditions

This calculation is valid under the following conditions:

  • Calore specifico costante nell'intervallo di temperatura considerato
  • Flusso stazionario (regime permanente)
  • Nessuna variazione di fase (solo calore sensibile, non latente)

This calculation is valid when: Calore specifico costante nell'intervallo di temperatura considerato; Flusso stazionario (regime permanente); Nessuna variazione di fase (solo calore sensibile, non latente).

The result is indicative. Verify against applicable codes and standards with a licensed professional before applying to a real project.

All inputs and outputs use SI units. Convert any values in other unit systems before entering them.

Limitations

This calculation does not apply in the following cases:

  • Per vapore o fluidi bifase usare l'entalpia specifica, non cp × ΔT
  • cp dell'acqua varia con la temperatura: 4217 J/(kg·K) a 0°C, 4181 a 20°C, 4216 a 80°C — usare 4186 come valore medio approssimato

Per vapore o fluidi bifase usare l'entalpia specifica, non cp × ΔT

cp dell'acqua varia con la temperatura: 4217 J/(kg·K) a 0°C, 4181 a 20°C, 4216 a 80°C — usare 4186 come valore medio approssimato

Referenced standards

  • UNI EN ISO 13790
  • UNI 10339 Impianti aeraulici

Formula source: Q = ṁ × cp × ΔT. Termodinamica classica. UNI EN ISO 13790, ASHRAE Handbook Fundamentals.

Formula: Q [W] = ṁ [kg/s] × cp [J/(kg·K)] × ΔT [K] — Source: Q = ṁ × cp × ΔT. Termodinamica classica. UNI EN ISO 13790, ASHRAE Handbook Fundamentals. — Standards: UNI EN ISO 13790 · UNI 10339 Impianti aeraulici — Domain risk: advisory

Application examples

1

Impianto idronico 0.5 kg/s, ΔT=10°C

Impianto di riscaldamento domestico con acqua, portata 30 l/min, ΔT mandata-ritorno 10°C

Parameters: Portata massica (kg/s) 0.5 kg/s · Calore specifico cp [J/(kg·K)] 4,186 J/(kg·K) · Differenza di temperatura (K o °C) 10 K
Results: Potenza termica (W) 20,930 W · Potenza termica (kW) 20.93 kW
2

UTA 5 kg/s aria, ΔT=15°C

Unità di trattamento aria in impianto di ventilazione industriale

Parameters: Portata massica (kg/s) 5 kg/s · Calore specifico cp [J/(kg·K)] 1,005 J/(kg·K) · Differenza di temperatura (K o °C) 15 K
Results: Potenza termica (W) 75,375 W · Potenza termica (kW) 75.375 kW

Frequently asked questions

What does the Sensible Thermal Power calculator compute?

Calculate sensible heating/cooling power: Q = ṁ × c_p × ΔT. For HVAC air handling unit sizing and heat exchanger preliminary design.

When is this calculation valid?

This calculation is valid under the following conditions: Calore specifico costante nell'intervallo di temperatura considerato; Flusso stazionario (regime permanente); Nessuna variazione di fase (solo calore sensibile, non latente).

When is this calculator not appropriate?

Per vapore o fluidi bifase usare l'entalpia specifica, non cp × ΔT cp dell'acqua varia con la temperatura: 4217 J/(kg·K) a 0°C, 4181 a 20°C, 4216 a 80°C — usare 4186 come valore medio approssimato

How accurate is the result?

This calculator implements the standard form of the formula. Accuracy depends on the quality of the inputs provided. Source: Q = ṁ × cp × ΔT. Termodinamica classica. UNI EN ISO 13790, ASHRAE Handbook Fundamentals..

What is the source of the formula?

Q = ṁ × cp × ΔT. Termodinamica classica. UNI EN ISO 13790, ASHRAE Handbook Fundamentals. Referenced standards: UNI EN ISO 13790, UNI 10339 Impianti aeraulici.

Which parameter has the greatest influence on the result?

"Differenza di temperatura (K o °C)" is the most influential parameter: a 10% change in this input produces approximately 10% change in "Potenza termica (W)".

How does the result change under different conditions?

Comparison between "Reference conditions" and "Impianto idronico 0.5 kg/s, ΔT=10°C": Potenza termica (W) [W]: decreases by 50.0% (from 41860.000 to 20930.000). Potenza termica (kW) [kW]: decreases by 50.0% (from 41.860 to 20.930).

Technical note

Per impianti idronici con acqua (cp ≈ 4186 J/(kg·K)): regola pratica Q(kW) ≈ portata(l/s) × ΔT(°C) × 4.186. Con ΔT=10°C: Q ≈ portata(l/s) × 41.86 kW/l/s.

Technical note

Per impianti aeraulici con aria (cp ≈ 1005 J/(kg·K), ρ ≈ 1.2 kg/m³): Q(W) = portata(m³/s) × 1200 × ΔT(°C).

Technical note

Conversione portata volumetrica → massica: per acqua a 20°C, 1 l/min = 1/60 l/s ≈ 0.01667 kg/s.

Technical deep dive

About this calculator

Calculate sensible heating/cooling power: Q = ṁ × c_p × ΔT. For HVAC air handling unit sizing and heat exchanger preliminary design.

Formula

Q [W] = ṁ [kg/s] × cp [J/(kg·K)] × ΔT [K]

Validity conditions

This calculation is valid under the following conditions:

  • Calore specifico costante nell'intervallo di temperatura considerato
  • Flusso stazionario (regime permanente)
  • Nessuna variazione di fase (solo calore sensibile, non latente)

Result sensitivity

The result varies significantly with changes in the following parameters:

  • Differenza di temperatura (K o °C) [K]: linear sensitivity on "Potenza termica (W)" (proportional, elasticity 1.00).
  • Portata massica (kg/s) [kg/s]: linear sensitivity on "Potenza termica (W)" (proportional, elasticity 1.00).
  • Calore specifico cp [J/(kg·K)] [J/(kg·K)]: linear sensitivity on "Potenza termica (W)" (proportional, elasticity 1.00).

When this calculator does not apply

  • Per vapore o fluidi bifase usare l'entalpia specifica, non cp × ΔT
  • cp dell'acqua varia con la temperatura: 4217 J/(kg·K) a 0°C, 4181 a 20°C, 4216 a 80°C — usare 4186 come valore medio approssimato

Technical notes

  • Per impianti idronici con acqua (cp ≈ 4186 J/(kg·K)): regola pratica Q(kW) ≈ portata(l/s) × ΔT(°C) × 4.186. Con ΔT=10°C: Q ≈ portata(l/s) × 41.86 kW/l/s.
  • Per impianti aeraulici con aria (cp ≈ 1005 J/(kg·K), ρ ≈ 1.2 kg/m³): Q(W) = portata(m³/s) × 1200 × ΔT(°C).
  • Conversione portata volumetrica → massica: per acqua a 20°C, 1 l/min = 1/60 l/s ≈ 0.01667 kg/s.

Technical analysis

Method: Calculate sensible heating/cooling power: Q = ṁ × c_p × ΔT. For HVAC air handling unit sizing and heat exchanger preliminary design.

Reference result: Potenza termica (W): 41860.000 W, Potenza termica (kW): 41.860 kW.

Note: Technical support tool. Results do not replace design verification by a licensed professional engineer.

Sensitivity analysis

Elasticity: percentage change in output relative to percentage change in input (1.0 = linear).

InputPrimary outputElasticityRelationship
Differenza di temperatura (K o °C) [K] Potenza termica (W) 1.00 linear
Portata massica (kg/s) [kg/s] Potenza termica (W) 1.00 linear
Calore specifico cp [J/(kg·K)] [J/(kg·K)] Potenza termica (W) 1.00 linear
Comparison between "Reference conditions" and "Impianto idronico 0.5 kg/s, ΔT=10°C": Potenza termica (W) [W]: decreases by 50.0% (from 41860.000 to 20930.000). Potenza termica (kW) [kW]: decreases by 50.0% (from 41.860 to 20.930).

Note: The result is particularly sensitive to "Differenza di temperatura (K o °C)" [K]: a 10% change produces approximately 10% change in "Potenza termica (W)".

Calore specifico costante nell'intervallo di temperatura considerato
Flusso stazionario (regime permanente)
Nessuna variazione di fase (solo calore sensibile, non latente)
Per vapore o fluidi bifase usare l'entalpia specifica, non cp × ΔT
cp dell'acqua varia con la temperatura: 4217 J/(kg·K) a 0°C, 4181 a 20°C, 4216 a 80°C — usare 4186 come valore medio approssimato
Technical support tool. Results do not replace design verification by a licensed professional engineer.